Quantcast
Industry Cortex

Document Brief

Electropneumatic Transducer (I/P, E/P)...

Installation, Operation and Maintenance Instructions...

Ordering Information...

Type 500X I/P Transducers...

Part Number 500-AA 500-AB 500-AC 500-AD 500-AE 500-AF 500-BC 500-BD 500-BE 500-AG 500-AH 500-BF Input 4-20 mA 4-20 mA 4-20 mA 4-20 mA 4-20 mA 4-20 mA 10-50 mA 10-50 mA 10-50 mA 4-20 mA 4-20 mA 0-60 mA Output Range psi kPa 3-9 9-15 3-15 3-27 6-30 1-17 3-15 3-27 6-30 2-60 3-120 2-120 20-60 60-100 20-100 20-185 40-200 7-117 20-100 20-185 40-200 14-420 20-830 15-830 Impedance 90 Ohms 90 Ohms 180 Ohms 220 Ohms 220 Ohms 250 Ohms 70 Ohms 85 Ohms 85 Ohms 225 Ohms 260 Ohms 220 Ohms...

Pilot Pressure Atmospheric Pressure Supply Pressure Output Pressure...

Section 1.0 Description Description & Installation Operation Maintenance Troubleshooting Warranty Page 2 3 5 5 5...

Type 500X E/P Transducers...

Part Number 500-CC 500-CD 500-CE 500-DC 500-DD 500-DE 500-CF 500-EH Input 0-5 VDC 0-5 VDC 0-5 VDC 1-9 VDC 1-9 VDC 1-9 VDC 0-5 VDC 0-10 VDC Output Range psi kPa 3-15 3-27 6-30 3-15 3-27 6-30 2-60 3-120 20-100 20-185 40-200 20-100 20-185 40-200 14-420 20-830 Impedance 615 Ohms 530 Ohms 530 Ohms 985 Ohms 840 Ohms 840 Ohms 500 Ohms 805 Ohms...

2.0 3.0 4.0 5.0...

Output shown is as calibrated at the factory. Large span adjustment capability allows recalibration to achieve output ranges from 3-35 psig (20-240 kPa) with 260 psig unit to 3-145 psig (20-1000 kPa) with 2-120 psig unit....

8 Columbia Drive Amherst, NH 03031 USA 603-886-9400 Fax 603-889-1844 www.controlair.com sales@controlair.com...

Type 500X Page 1...

441-622-015...

DANGER, WARNING, CAUTION and NOTE statements...

DANGER WARNING CAUTION NOTE...

Refers to conditions or hazards which could result in serious personal injury or death. Refers to conditions or hazards which could result in personal injury. Refers to conditions or hazards which could result in equipment or property damage. Alerts you to facts or special instructions....

ALL DANGER, WARNING, AND CAUTION NOTICES MUST BE COMPLIED WITH IN FULL...

SPECIFICATIONS...

Min./Max. Supply Pressure Minimum - 3 psig (21 kPa) Above maximum output Maximum - 100 psig (700 kPA) < 0.1% of span per psig (< 0.15% of span per 10 kPa) < 0.75% of span < 0.5% of span < 1.0% of span 4.5 scfm (7.6 m3/hr ANR) at 25 psig (175 kPa) supply 12.0 scfm (20.0 m3/hr ANR) at 100 psig (700 kPa) supply Maximum Air Consumption Port Sizes .05 scfm (.07 m3/hr) midrange typical 1/4 NPT (Pneumatic) 1/2 NPT (Electric)...

Supply Pressure Sensitivity Linearity Repeatability...

Document Keywords

Instructions downloads 500 instr

Sponsored Products

About ControlAir, Inc.

ControlAir, Inc. manufactures custom air regulators precision pneumatic control products such as electropneumatic controls, air pressure regulators, current - to - pressure (I/P) transducers, voltage...

Contact

603-886-9400, 800-216-3636 (toll free)
Fax: 603-889-1844

sponsored links